Document IIF

Modèle hybride d'évaluation des fuites fiable sur le plan des calculs, pour les compresseurs volumétriques et les détendeurs.

A computationally efficient hybrid leakage model for positive displacement compressors and expanders.

Auteurs : BELL I. H., GROLL E. A., BRAUN J. E., et al.

Type d'article : Article, Article de la RIF

Résumé

An empirical frictional correction factor to the isentropic nozzle model has been developed for application to refrigerant leakage modeling in scroll, rotary and other similar compressors and expanders. This correction factor is derived by calculating the leakage mass flow rate with a compressible, variable area, real gas properties model and referencing the results to an isentropic nozzle model. The ratio of flows is correlated to the Reynolds number, a characteristic length and the leakage gap width. A representative selection of fluids and geometries are employed. For all the correlations, at least 93% of the points are predicted within an absolute error band of 20%.

Documents disponibles

Format PDF

Pages : 1965-1973

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : A computationally efficient hybrid leakage model for positive displacement compressors and expanders.
  • Identifiant de la fiche : 30009785
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 7
  • Date d'édition : 11/2013

Liens