Document IIF

Modélisation de l'écoulement non adiabatique à l'intérieur des capillaires : approche simplifiée et validation expérimentale complète.

Modelling of non-adiabatic capillary tube flows: a simplified approach and comprehensive experimental validation.

Auteurs : HERMES C. J. L., MELO C., GONÇALVES J. M.

Type d'article : Article, Article de la RIF

Résumé

A simplified computational model for simulating refrigerant flow through capillary tubes is proposed and validated using a dataset composed of more than 1400 experimental data points, including adiabatic flows of refrigerants CFC-12, HCFC-22, HFC-134a, HC-600a, R-404A, R-407C and R-507A, and non-adiabatic flows of refrigerants HFC-134a and HC-600a, in both concentric and lateral capillary tube-suction line heat exchanger configurations. The model is based on the mass, energy and momentum conservation equations written according to their one-dimensional differential formulation. Some simplifications were added to the model in order to improve both numerical stability and computational performance. It was found that the model predicts 91.5% of the measured refrigerant mass flow rate for adiabatic and 79.3% for non-adiabatic flows within an error band of ±10%. Also, the model solves non-adiabatic flows as fast as adiabatic ones.

Documents disponibles

Format PDF

Pages : 1358-1367

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Modelling of non-adiabatic capillary tube flows: a simplified approach and comprehensive experimental validation.
  • Identifiant de la fiche : 2009-0138
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 8
  • Date d'édition : 12/2008

Liens


Voir d'autres articles du même numéro (15)
Voir la source