Document IIF

Modélisation de la performance des refroidisseurs à deux lits à adsorption utilisant le gel de silice/eau + erratum.

Modelling the performance of two-bed, silica gel-water adsorption chillers + erratum.

Auteurs : CHUA H. T., NG K. C., MALEK A., KASHIWAGI T., AKISAWA A., SAHA B.

Type d'article : Article, Article de la RIF

Résumé

The article presents a transient model for a two-bed, silica gel-water adsorption chiller. Compared with their previous cyclic-steady-state model, the authors found very good agreement between their model prediction and experimental data. They found that, regardless of the initial mass distribution, the chiller was able to achieve the same cyclic-steady state within four cycles or 1800 s. They also demonstrated that the manufacturer had empirically evolved to select a fixed switching and cycle time such that the best peak evaporator temperature suppression, and near maximum cooling capacity can be achieved by a compact design.

Documents disponibles

Format PDF

Pages : 194-204

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Modelling the performance of two-bed, silica gel-water adsorption chillers + erratum.
  • Identifiant de la fiche : 1999-2901
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 22 - n. 3
  • Date d'édition : 05/1999

Liens