MODELISATION PAR ORDINATEUR D'UN SYSTEME DE CONDITIONNEMENT D'AIR A ACCUMULATION STRUCTURELLE.

COMPUTER MODELLING OF A STRUCTURAL STORAGE AIR-CONDITIONING SYSTEM.

Résumé

ON PRESENTE LE DEVELOPPEMENT D'UN MODELE DE SIMULATION PAR ORDINATEUR D'UN SYSTEME DE CONDITIONNEMENT D'AIR A ACCUMULATION STRUCTURELLE. LE MODELE FONDE SUR DES RECHERCHES EXPERIMENTALES RELATIVES AUX CONFIGURATIONS DES ECOULEMENTS DE L'AIR ET AUX TAUX DE TRANSFERT DE CHALEUR, DANS UN FAUX-PLANCHER, A ETE UTILISE POUR ETUDIER L'EFFET DE PLUSIEURS PARAMETRES DE CONCEPTION SUR LA PERFORMANCE DU SYSTEME. DES SIMULATIONS ONT ETE EFFECTUEES POUR UNE JOURNEE ET POUR L'ANNEE ENTIERE, POUR UN IMMEUBLE FICTIF DANS DIVERSES LOCALISATIONS GEOGRAPHIQUES EN AFRIQUE DU SUD. PAR RAPPORT A UN SYSTEME A DEBIT D'AIR VARIABLE, DES REDUCTIONS DE LA CHARGE DE POINTE DE 12 A 16 WATTS PAR M2 AINSI QUE DES ECONOMIES MENSUELLES D'ELECTRICITE DE 300 A 950 WATTHEURES PAR M2 (1,08 A 3,42 MEGAJOULES/METRE CARRE) POUR LES MOIS D'ETE, PEUVENT ETRE REALISEES GRACE AU SYSTEME MODELISE.

Détails

  • Titre original : COMPUTER MODELLING OF A STRUCTURAL STORAGE AIR-CONDITIONING SYSTEM.
  • Identifiant de la fiche : 1991-1691
  • Langues : Anglais
  • Date d'édition : 23/04/1990
  • Source : Source : ASHRAE-FRIGAIR '90, Pretoria
    vol. 1; pap. A.4; 11 p.; 3 fig.; 2 tabl.; 4 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.