Document IIF

Modélisation transitoire d'un système de pompe à chaleur à injection de vapeur [avec réservoir à vaporisation instantanée]. 2. Résultats de la simulation et validation expérimentale.

Transient modeling of a flash tank vapor injection heat pump system. 2. Simulation results and experimental validation.

Auteurs : QIAO H., XU X., AUTE V., et al.

Type d'article : Article, Article de la RIF

Résumé

This two-part article investigates the transient characteristics of a flash tank vapor injection system through modeling and experimental validation. The first part describes the detailed modeling techniques for each component, and the second part describes the transient simulations that are carried out for the overall system under start-up and shut-down operations and presents the results. After comparing the predictions of the proposed model with the experimental data, it was concluded that the proposed model can adequately capture the transient heat transfer and flow phenomena of the system. The dynamic system response when subjected to a step change in the opening of the upper-stage EEV (electronic expansion valve) was also investigated. It was found that EEV opening has a significant impact on the system performance and the liquid level in the flash tank, but exhibits little effect on the suction pressure. These findings were corroborated through experiments.

Documents disponibles

Format PDF

Pages : 183-194

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Transient modeling of a flash tank vapor injection heat pump system. 2. Simulation results and experimental validation.
  • Identifiant de la fiche : 30013056
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 49
  • Date d'édition : 01/2015

Liens


Voir d'autres articles du même numéro (18)
Voir la source