Résumé

A performance predicting model of screw compressors, for refrigeration system simulation, is developed. The model correlates the running condition and some of the design parameters of a screw compressor. Compared with the experimental data, the errors of the model predictions are about ±2% for the volumetric displacement, less than 3% for the input power at full load condition, about 4% for the input power at part-load displacement condition, and about 2% and less than 4% for vapor injection mass flowrate. This model can also be used to optimize the built-in volumetric ratio of a screw compressor.

Documents disponibles

Format PDF

Pages : 861-870

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : A new model of screw compressor for refrigeration system simulation.
  • Identifiant de la fiche : 30004001
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 35 - n. 4
  • Date d'édition : 06/2012