Numerical investigation of transfer coefficients of an evaporatively-cooled condenser.
Auteurs : JAHANGEER K. A., TAY A. A. O., ISLAM M. R.
Type d'article : Article
Résumé
Vapour compression cooling systems working in tropical climatic conditions make the compressor pressure-lift relatively high. The lowering of the condensing temperature will help reduce this lift, thereby reducing the power required by the compressor. The inclusion of water sprays or droplets in aircooled condensers is a possible option for improving the performance of the condenser by reducing the temperature lift. This paper reports a numerical investigation of the heat transfer characteristics of an evaporatively-cooled condenser. A detailed model is developed and numerical simulations are carried out using finite difference techniques. The simulations are performed for a single unfinned tube of the condenser with the air flowing across the tube. Water is sprayed on top of the tube in the form of fine sprays and the flow rate is set to achieve film thicknesses of 0.075, 0.1, and 0.15 mm, respectively. The tube wall temperature is assumed constant due to the fact that for most of the tube length, condensation of the refrigerant occurs at the saturation temperature of the refrigerant. Wall to air overall heat transfer coefficient (U) value as high as 2000 W/m2 K is observed with the incorporation of the evaporative cooling. The numerical results are compared with available experimental and theoretical work and the agreement is found to be satisfactory. [Reprinted with permission from Elsevier. Copyright, 2011].
Détails
- Titre original : Numerical investigation of transfer coefficients of an evaporatively-cooled condenser.
- Identifiant de la fiche : 30004007
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 31 - n. 10
- Date d'édition : 07/2011
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2011.02.007
Liens
Voir d'autres articles du même numéro (10)
Voir la source
-
Simultaneous heat and mass transfer in a wetted...
- Auteurs : ZHANG F., BOCK J., JACOBI A. M., et al.
- Date : 16/07/2012
- Langues : Anglais
- Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Waardoor wordt de werking van een dauwpuntkoele...
- Auteurs : JANSSEN M., UGES P. G. H.
- Date : 12/2010
- Langues : Néerlandais
- Source : Koude & Luchtbehandeling - vol. 103
Voir la fiche
-
Studying the performance of an improved dew-poi...
- Auteurs : CUI X., CHUA K. J., YANG W. M., et al.
- Date : 02/2014
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 63 - n. 2
Voir la fiche
-
Theoretical analysis and experimental design of...
- Auteurs : GU Y., ZOU Y., PAN S., et al.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche
-
Innovatief en duurzaam koelen met hybride droge...
- Auteurs : QUADFLIEG J.
- Date : 10/2010
- Langues : Néerlandais
- Source : Koude & Luchtbehandeling - vol. 103
Voir la fiche