Optimisation d'un système de pompe à chaleur à absorption à gaz.

Optimización de un sistema de bomba de calor de absorción con gas.

Auteurs : CORRALES CIGANDA J. L., GRAF R., KÜHN A., et al.

Type d'article : Article, Étude de cas

Résumé

In the course of an energy-efficient modernization of a kindergarten in Berlin a 35 kW gas absorption heat pump using NH3/H2O as working pair has been installed in 2010. Domestic hot water production and space heating are additionally supported by a 15 m2 solar collector. The low temperature heat is supplied to the heat pump system by four 100 m long vertical ground probes. In this paper operation data for the period 2011-2012 are presented. Gas Utilization Efficiencies (GUE) are calculated and compared for different demand profiles. The comparison of measured GUE. values with manufacturer data revealed potential for system optimization. Based on operation analysis modifications of the control strategy and alternative hydraulic set-ups for an improved performance are presented.

Documents disponibles

Format PDF

Pages : 24-32 (9 p.)

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Optimización de un sistema de bomba de calor de absorción con gas.
  • Identifiant de la fiche : 30011520
  • Langues : Espagnol
  • Source : Frío Calor Aire acondicionado - vol 42, n. 468
  • Date d'édition : 04/2014

Liens


Voir la source