Optimisation financière et conception de systèmes de pompes à chaleur hybrides couplées au sol.
Financial optimization and design of hybrid ground-coupled heat pump systems.
Auteurs : HÉNAULT B., PASQUIER P., KUMMERT M.
Type d'article : Article
Résumé
A strategy to optimize the net present value of a hybrid ground-coupled heat pump system is presented. The method relies on a spectral-based simulation tool that predicts the heat pump performance on an hourly basis and on a optimization algorithm. The approach considers the project financial parameters, the hourly thermal load of the building, the pumping energy, the control strategy, the design fluid temperature of the heat pumps, the ground thermal properties, the footprint available for the ground heat exchanger, the local construction and equipment costs as well as complex electricity rates such as demand charges and energy. The proposed method gives the optimal number and location of the vertical boreholes, the number of required heat pumps and their operating temperature limits as well as the optimal energy savings generated by the ground-coupled heat pump system. Results indicate that fine tuning some design parameters such as the number of boreholes and installed heat pumps or the temperature limit in heating mode can significantly improve the financial performance of a project. Additionally, results confirm that use of hybrid systems could reduce significantly the electrical consumption and peak electrical load of a building.
Détails
- Titre original : Financial optimization and design of hybrid ground-coupled heat pump systems.
- Identifiant de la fiche : 30017014
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 93
- Date d'édition : 25/01/2016
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2015.09.088
Liens
Voir d'autres articles du même numéro (72)
Voir la source
Indexation
-
Energy efficiency of variable capacity ground s...
- Auteurs : MUNARI P., DA RIVA E., DEL COL D., et al.
- Date : 05/04/2011
- Langues : Anglais
- Source : Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
Voir la fiche
-
Análisis de intercambiadores de calor subterrán...
- Auteurs : CAURET O., DALICIEUX P.
- Date : 11/2009
- Langues : Espagnol
- Source : Frío Calor Aire acondicionado - vol. 37 - n. 419
- Formats : PDF
Voir la fiche
-
Analysis of ground heat exchangers for geotherm...
- Auteurs : CAURET O., DALICIEUX P.
- Date : 14/07/2008
- Langues : Anglais
- Source : 2008 Purdue Conferences. 19th International Compressor Engineering Conference at Purdue & 12th International Refrigeration and Air-Conditioning Conference at Purdue [CD-ROM].
- Formats : PDF
Voir la fiche
-
Suitability of foundation heat exchangers for g...
- Auteurs : CULLIN J. R., SPITLER J. D., GEHLIN S. E. A.
- Date : 01/2014
- Langues : Anglais
- Source : REHVA Journal - vol. 51 - n. 1
Voir la fiche
-
Heat dissipation effect on a borehole heat exch...
- Auteurs : DARKWA J., SU W., CHOW D. H. C.
- Date : 10/2013
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 60 - n. 1-2
Voir la fiche