Performance côté air des échangeurs de chaleur en aluminium brasés sous des conditions de déshumidification.

Air-side performance of brazed aluminum heat exchangers under dehumidifying conditions.

Auteurs : KIM M. H., BULLARD C. W.

Type d'article : Article, Article de la RIF

Résumé

An experimental study for air-side thermal-hydraulic performance of brazed aluminum heat exchangers under dehumidifying has been performed. For 30 samples of louvered fin heat exchangers with different geometrical parameters, the heat transfer and pressure drop characteristics for wet surface were evaluated. The test was conducted for air-side Reynolds number in the range of 80-300 and tube-side water flow rate of 320 kg/h. The dry- and wet-bulb temperatures of the inlet air for heat exchangers were 27 and 19 °C, respectively and the inlet water temperature was 6 °C. The air-side thermal performance data for cooling and dehumidifying conditions were analyzed using effectiveness-NTU method for cross-flow heat exchanger with both fluids unmixed. The test results are reported, compared with those for the dry surface heat exchangers, in terms of sensible j factor and friction factor f, as functions of Reynolds number based on louver pitch. The correlations for j and f factors are developed within rms errors of plus or minus 16.9 and plus or minus 13.6%, respectively.

Documents disponibles

Format PDF

Pages : 924-934

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Air-side performance of brazed aluminum heat exchangers under dehumidifying conditions.
  • Identifiant de la fiche : 2003-0688
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 25 - n. 7
  • Date d'édition : 11/2002