Performance d'un système de refroidissement à éjecteur avec un effet de pompage thermique utilisant le R141b et le R365mfc.

Performance of ejector cooling system with thermal pumping effect using R141b and R365mfc.

Auteurs : WANG J. H., WU J. H., HU S. S., et al.

Type d'article : Article

Résumé

The ejector cooling system (ECS) is suitable for solar cooling application due to its simple design and low cost. An ECS using a multi-function generator (ECS/MFG) as a thermal pumping device without rotating machines for refrigerant circulation has been designed and tested. The experiment of an ECS/MFG operating at full-cycle while using R141b has shown that the COP(o) can reach 0.225 and cooling capacity of 0.75 kW at generator temperature 90°C, condenser temperature 37°C, and evaporator temperature 8.5°C. This study also redesigned the ejector for working fluid R365mfc in order to replace R141b. This study has shown that R365mfc can replace R141b as the working fluid of ECS/MFG at no payoff of system performance as long as the ejector design is optimized. [Reprinted with permission from Elsevier. Copyright, 2008].

Détails

  • Titre original : Performance of ejector cooling system with thermal pumping effect using R141b and R365mfc.
  • Identifiant de la fiche : 2009-2045
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 29 - n. 10
  • Date d'édition : 07/2009
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2008.08.015