Performance d'une pompe à chaleur air-eau utilisant une injection de vapeur biétagée.

Performance of air-to-water heat pump using 2 stage vapour injection.

Numéro : pap. n. R8, 2475

Auteurs : KO Y., JIN S., HA S., et al.

Résumé

On the heat pump system, vapour injection (VI) compression cycle's superiority over non-injection cycle has been well known. VI system produces the high heating capacity, and its power consumption is less than the non-injection system. Furthermore, the system design of the vapour compression cycle also minimizes the compressor size. The investigation of VI cycle's influence on the air-to-water heat pump (AWHP) system is presented. At 35°C water temperature, VI AWHP improves 20% heating capacity and 10% COP compared to the conventional AWHP. At 60°C water temperature, VI AWHP improves 48% heating capacity and 12% COP compared to the conventional AWHP. Experimental results are compared at the same compressor displacement volume.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance of air-to-water heat pump using 2 stage vapour injection.
  • Identifiant de la fiche : 30000579
  • Langues : Anglais
  • Source : 2010 Purdue Conferences. 13th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Date d'édition : 12/07/2010

Liens


Voir d'autres communications du même compte rendu (121)
Voir le compte rendu de la conférence