Performance des côtés air sec et air humide d'un échangeur de chaleur à ailettes persiennées et tubes plats.

Dry and wet air-side performance of a louver-finned heat exchanger having flat tubes.

Auteurs : KIM N. H., KIM S. H., BYUN H. W., et al.

Résumé

A louver-finned flat tube heat exchanger was tested, and the data are compared with those of the state-of-the-art round tube heat exchanger. Both heat exchangers have the same tube perimeter and fin pitch. Tests were conducted under dry and wet conditions. The results show that, under dry condition, both j and f factors of the round tube heat exchanger are larger than those of the flat tube heat exchanger. As the Reynolds number decreases, however, j and f factors of the flat tube heat exchanger increase at steeper slopes than those of the round tube heat exchanger.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Dry and wet air-side performance of a louver-finned heat exchanger having flat tubes.
  • Identifiant de la fiche : 2011-0085
  • Langues : Anglais
  • Date d'édition : 12/07/2010
  • Source : Source : Proc. 2010 int. Refrig. Air Cond. Conf., Purdue Univ.
    n. 2185; 8 p.; fig.; photogr.; tabl.; 14 ref.