Document IIF
Performance des systèmes à compression de vapeur munis de compresseurs avec suralimentation en huile et régénération.
Performance of vapour compression systems with compressor oil flooding and regeneration.
Auteurs : BELL I. H., GROLL E. A., BRAUN J. E.
Type d'article : Article, Article de la RIF
Résumé
Vapour compression refrigeration technology has seen great improvement over the last several decades in terms of cycle efficiency through a concerted effort of manufacturers, regulators, and research engineers. As the standard vapour compression systems approach practical limits, cycle modifications should be investigated to increase system efficiency and capacity. One possible means of increasing cycle efficiency is to flood the compressor with a large quantity of oil to achieve a quasi-isothermal compression process, in addition to using a regenerator to increase refrigerant subcooling. In theory, compressor flooding and regeneration can provide a significant increase in system efficiency over the standard vapour compression system. The effectiveness of compressor flooding and regeneration increases as the temperature lift of the system increases. Therefore, this technology is particularly well suited towards lower evaporating temperatures and high ambient temperatures as seen in supermarket refrigeration applications. While predicted increases in cycle efficiency are over 40% for supermarket refrigeration applications, this technology is still very beneficial for typical air-conditioning applications, for which improvements in cycle efficiency greater than 5% are predicted. It has to be noted though that the beneficial effects of compressor flooding can only be realized if a regenerator is used to exchange heat between the refrigerant vapour exiting the evaporator and the liquid exiting the condenser.
Documents disponibles
Format PDF
Pages : pp. 225-233
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Performance of vapour compression systems with compressor oil flooding and regeneration.
- Identifiant de la fiche : 2010-1424
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 1
- Date d'édition : 01/2011
Liens
Voir d'autres articles du même numéro (36)
Voir la source
Indexation
-
Influence of compressor oil admixtures on theor...
- Auteurs : ZHELEZNY V. P., NICHENKO S. V., SEMENYUK Y. V.
- Date : 11/2009
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 7
- Formats : PDF
Voir la fiche
-
Fondamenti di base sulla refrigerazione.
- Auteurs : BILIERO L.
- Date : 2006
- Langues : Italien
- Source : Industria & Formazione - vol. 30 - n. 7
- Formats : PDF
Voir la fiche
-
Suction pressure: how important is it?
- Auteurs : SNYDER D.
- Date : 27/01/1992
- Langues : Anglais
- Source : Air Cond. Heat. Refrig. News - vol. 185 - n. 4
Voir la fiche
-
Vergleich Schraubenverdichter-Turboverdichter: ...
- Auteurs : KADEN P.
- Date : 03/2008
- Langues : Allemand
- Source : Kälte + Klimatechnik (Die) - vol. 61 - n. 3
Voir la fiche
-
A study on the operational stability of a refri...
- Auteurs : CHEN Y., DENG S., XU X., et al.
- Date : 12/2008
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 8
- Formats : PDF