Document IIF

Performance énergétique et exergétique des fluides de Bethe-Zeldovich-Thompson (BZT) utilisés pour les pompes à chaleur géothermiques.

Energetic and exergetic performance analysis of Bethe-Zeldovich-Thompson (BZT) fluids in geothermal heat pumps.

Auteurs : OZCAN O., OZGENER O.

Type d'article : Article, Article de la RIF

Résumé

This study highlights theoretical energetic and exergetic performance evaluation results of Bethe-Zeldovich-Thompson (BZT) fluids in geothermal heat pumps. In this study, hexafluoroethane (R116), octafluoropropane (R218), and octafluorocyclobutane (RC318) were selected as possible alternative replacements to the traditional refrigerants in geothermal heat pumps. According to the calculations, coefficient of performance of 101 kW geothermal heat pumps (COPHP) changes with range between 3.84, 3.08, and 2.92 for octafluorocyclobutane (RC318), hexafluoroethane (R116), and octafluoropropane (R218), respectively. Moreover, R116 shows the maximum exergy efficiency 68% among the selected BZT fluids.

Documents disponibles

Format PDF

Pages : 1943-1952

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Energetic and exergetic performance analysis of Bethe-Zeldovich-Thompson (BZT) fluids in geothermal heat pumps.
  • Identifiant de la fiche : 30002287
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 8
  • Date d'édition : 12/2011

Liens


Voir d'autres articles du même numéro (40)
Voir la source