In this study, thermodynamic performance of R432A and HCFC-22 is measured in a heat pump bench tester under both air-conditioning and heat pumping conditions. R432A has no ozone depletion potential and very low greenhouse warming potential of less than 5. R432A also offers a similar vapour pressure to HCFC-22 for 'drop-in' replacement. Test results showed that the coefficient of performance and capacity of R432A are 8.5-8.7% and 1.9-6.4% higher than those of HCFC-22 for both conditions. The compressor discharge temperature of R432A is 14.1-17.3°C lower than that of HCFC-22 while the amount of charge for R-432A is 50% lower than that of HCFC-22 due to its low density. Overall, R432A is a good long term 'dropin' environmentally friendly alternative to replace HCFC-22 in residential air-conditioners and heat pumps due to its excellent thermodynamic and environmental properties. [Reprinted with permission from Elsevier. Copyright, 2008].
Détails
- Titre original : Experimental performance of R432A to replace R22 in residential air conditioners and heat pumps.
- Identifiant de la fiche : 2009-0537
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 29 - n. 2-3
- Date d'édition : 02/2009
Liens
Voir d'autres articles du même numéro (4)
Voir la source
Indexation
- Thèmes : HCFC
- Mots-clés : R432a; R22; Propriété thermodynamique; Substitut; Pompe à chaleur; Experimentation; Frigorigène; Conditionnement d'air
-
Thermodynamics and performance potential of R410A.
- Auteurs : BIVENS D. B., YOKOZEKI A.
- Date : 21/10/1996
- Langues : Anglais
- Source : International Conference on Ozone Protection Technologies. Conference proceedings.
Voir la fiche
-
Caractéristiques et utilisations du R410A.
- Auteurs : BLANC J., EURY S.
- Date : 05/2000
- Langues : Français
- Source : Rev. gén. Froid - vol. 90 - n. 1003
Voir la fiche
-
Prestaciones del R432A al sustituir el HCFC-22 ...
- Auteurs : PARK K. J., LEE C. H., JUNG D.
- Date : 10/2009
- Langues : Espagnol
- Source : Frío Calor Aire acondicionado - vol. 37 - n. 418
- Formats : PDF
Voir la fiche
-
Performance of R-432A to replace HCFC-22 in res...
- Auteurs : PARK K. J., LEE C. H., JUNG D.
- Date : 14/07/2008
- Langues : Anglais
- Source : 2008 Purdue Conferences. 19th International Compressor Engineering Conference at Purdue & 12th International Refrigeration and Air-Conditioning Conference at Purdue [CD-ROM].
- Formats : PDF
Voir la fiche
-
Properties and performance of Suva AC9000 in ai...
- Date : 01/1994
- Langues : Anglais
- Source : Du Pont de Nemours int. - n. 14
Voir la fiche