Performances d’un compresseur à spirale fonctionnant avec des frigorigènes de remplacement immédiat du R134a.
Performance of a scroll compressor working with drop-in refrigerant replacements to R134a.
Numéro : 1491
Auteurs : CONTE R., AZZOLIN M., BERNARDINELLO S., DEL COL D.
Résumé
Most of the countries around the world are adopting regulations and actions to reduce the use of hydrofluorocarbon (HFC) refrigerants with high Global Warming Potential (GWP). Among the HFCs, R134a, which has a GWP100years equal to 1530, is recognized by the IPCC as a major contributor and its atmospheric abundance increased by 71 % from 2011 to 2019. This work presents an experimental study on the performance of a new scroll compressor operating with six low-GWP refrigerants as drop-in alternatives to R134a. The refrigerants used are: R1234ze(E), R152a, R516A, R515B, R450A and R513A. The test system is a water-to-water chiller working with two large scroll compressors (swept volume for each compressor equal to 222.5 m3 h-1) and two brazed plate heat exchangers as the condenser and the evaporator. The experimental tests were conducted by fixing the inlet/outlet water temperatures in the heat exchangers when producing cold water at 7°C and 18°C. The data allow to evaluate and assess the compressor performance in terms of volumetric efficiency and global isentropic efficiency. Numerical correlations of Pierre (1982) and Navarro et al. (2013) to estimate the compressor efficiencies have been compared against the experimental data and new coefficients have been determined for those correlations.
Documents disponibles
Format PDF
Pages : 10
Disponible
Gratuit
Détails
- Titre original : Performance of a scroll compressor working with drop-in refrigerant replacements to R134a.
- Identifiant de la fiche : 30033623
- Langues : Anglais
- Sujet : Réglementation
- Source : 2024 Purdue Conferences. 27th International Compressor Engineering Conference at Purdue.
- Date d'édition : 18/07/2024
Liens
Voir d'autres communications du même compte rendu (80)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
HFC;
Compresseurs - Mots-clés : R134a; R152a; R450A; R516A; Frigorigène; Compresseur à spirale; Échangeur de chaleur; R1234ze; R513A; R515B
-
Experimental study of low-GWP refrigerants in a...
- Auteurs : AZZOLIN M., CONTE R., BERNARDINELLO S., DEL COL D.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche
-
A study of low GWP refrigerants for transport r...
- Auteurs : SJOHOLM L., MA Y. C.
- Date : 09/07/2018
- Langues : Anglais
- Source : 2018 Purdue Conferences. 24th International Compressor Engineering Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Utilisation du R134a dans les compresseurs rota...
- Auteurs : SIMONIN D.
- Date : 08/12/1992
- Langues : Français
Voir la fiche
-
Character analysis of refrigerant in AC and pre...
- Auteurs : PENG X., HUA Z., ZHUANG D.
- Date : 20/07/2017
- Langues : Anglais
- Source : 8th international conference on compressors and refrigeration, 2017.
- Formats : PDF
Voir la fiche
-
Mise au point d'un compresseur compact à spiral...
- Auteurs : HIRANO H., FUTAGAMI Y., OKA H.
- Date : 26/11/1998
- Langues : Japonais
- Source : Proceedings of the International symposium on HCFC alternative refrigerants '98: latest technology for higher performance and higher efficiency air conditioning and refrigeration equipment to the 21st century.
Voir la fiche