Pompes à chaleur commerciales sol-air et sol-eau : anomalies de fonctionnement typiques.

Representative operating problems of commercial ground-source and groundwater-source heat pumps.

Résumé

The paper describes representative problems encountered with commercial geothermal systems in the northeastern United States and describes some steps taken to correct these problems. Of the 23 buildings studied, 9 had problems caused by design or construction errors that were not related to geothermal technology. Poor or outdated geothermal design was the underlying cause of the difficulties in another 11, and errors in construction of the system accounted for the remaining 3. All of the problems studied would have been discovered and corrected by proper start-up and commissioning.

Détails

  • Titre original : Representative operating problems of commercial ground-source and groundwater-source heat pumps.
  • Identifiant de la fiche : 2001-2488
  • Langues : Anglais
  • Source : ASHRAE Transactions. 2000 ASHRAE Annual Meeting, Minneapolis, Minnesota + CD-ROM.
  • Date d'édition : 24/06/2000
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (49)
Voir le compte rendu de la conférence