Prévision de la performance d'un serpentin sous des conditions totalement et partiellement humides en employant la méthode de la température sèche.

Prediction of air coil performance under partially wet and totally wet cooling conditions using equivalent dry-bulb temperature method.

Auteurs : WANG J., HIHARA E.

Résumé

A new method, equivalent to a dry-bulb temperature method, is proposed for calculating the heat and mass transfer and for predicting the cooling modes (totally wet, partially wet, and totally dry) of moist air over the coil surface. A numeric model is further developed and validated with the experimental data of plain fin air coils. The deviation in both the cooling capacity and the vapour condensate estimated by the model is within the range of plus or minus 10%, and the prediction for the cooling modes of moist air over the coil surfaces is fairly exact.

Détails

  • Titre original : Prediction of air coil performance under partially wet and totally wet cooling conditions using equivalent dry-bulb temperature method.
  • Identifiant de la fiche : 2006-1420
  • Langues : Anglais
  • Source : Green breeze from Asia: frontiers of refrigerants, heat transfer and system.. ACRA-2002. Proceedings of the Asian conference on refrigeration and air conditioning.
  • Date d'édition : 04/12/2002

Liens


Voir d'autres communications du même compte rendu (50)
Voir le compte rendu de la conférence