Profil thermique d'un centre de données à haute densité : écoulement de chaleur aux points chauds de 512 W/ft2.
Thermal profile of a high-density data center: hot spot heat fluxes of 512 W/ft2.
Auteurs : SCHMIDT R., IYENGAR M., BEATY D., et al.
Résumé
This paper describes the thermal profile of a 23.2 × 29.9 m data center and the measurement techniques employed to fully capture the detailed thermal environment. In a portion of the data center 4.9 × 7.9 m, which encompasses very high powered servers, the heat flux is 5500 W/m2. Most racks within this area dissipated approximately 19 kW. Detailed measurements were taken in this data center of electronic equipment power usage, perforated floor tile airflow, cable cut-out airflow, computer room air-conditioning airflow, and electronic equipment inlet air temperatures. In addition to these measurements, the physical features of the data center were recorded such that a detailed CFD model could be employed to compare the results.
Détails
- Titre original : Thermal profile of a high-density data center: hot spot heat fluxes of 512 W/ft2.
- Identifiant de la fiche : 2006-3138
- Langues : Anglais
- Source : ASHRAE Transactions. 2005 Annual Meeting, Denver, Colorado, USA. Volume 111, part 2 + CD-ROM.
- Date d'édition : 2005
Liens
Voir d'autres communications du même compte rendu (23)
Voir le compte rendu de la conférence
Indexation
-
HVAC issues for data centres.
- Auteurs : PATTERSON M. K., STEINBRECHER R., MONTGOMERY S., et al.
- Date : 04/2005
- Langues : Anglais
- Source : ASHRAE Journal - vol. 47 - n. 4
Voir la fiche
-
Rack cooling effectiveness in data centers and ...
- Auteurs : HERRLIN M. K.
- Date : 2005
- Langues : Anglais
- Source : ASHRAE Transactions. 2005 Annual Meeting, Denver, Colorado, USA. Volume 111, part 2 + CD-ROM.
Voir la fiche
-
TECHNIQUE DE REFROIDISSEMENT DES ORDINATEURS EL...
- Auteurs : NAKAYAMA W.
- Date : 1987
- Langues : Japonais
- Source : Trans. JAR - vol. 4 - n. 2
Voir la fiche
-
Die freie Kühlung bei der Klimatisierung von DV...
- Auteurs : RUSCHKOWSKI G.
- Date : 04/2001
- Langues : Allemand
- Source : Kälte + Klimatechnik (Die) - vol. 54 - n. 4
Voir la fiche
-
Advances in CFD modelling for data centre optim...
- Auteurs : SILKE N., STANNUS W.
- Date : 10/2017
- Langues : Anglais
- Source : EcoLibrium - vol. 16 - n. 9
- Formats : PDF
Voir la fiche