Pulvérisation d'une solution binaire organique dans un système frigorifique à absorption.

Spray formation of binary organic solution for an absorption refrigeration system.

Auteurs : ORIAN G., JELINEK M., LEVY A.

Type d'article : Article

Résumé

In a triple-pressure-level absorption refrigeration system an ejector is incorporated between the evaporator and the absorber, in order to raise the pressure in the absorber to a middle pressure level by the pressure recovery achieved in the ejector diffuser. Higher pressure in the absorber at the same temperature means higher refrigerant concentration at the absorber outlet and by that means improving cycle performance. In order to examine the influence of a special nozzle device containing a spinner, and its geometry on the spray characteristics, an experimental system for generating and analyzing sprays of binary solutions (R22, chlorodifluoromethane and DMAC, dimethylacetamide) has been developed. The influence of spinner pitch angle and the number of wings at various pressure differences and temperatures on the spray characteristics, e.g., mean drop diameter, drop size distribution, drops velocity, spray cone angle and core length, is discussed. [Reprinted with permission from Elsevier. Copyright, 2005].

Détails

  • Titre original : Spray formation of binary organic solution for an absorption refrigeration system.
  • Identifiant de la fiche : 2006-2337
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 26 - n. 8-9
  • Date d'édition : 06/2006

Liens


Voir d'autres articles du même numéro (8)
Voir la source