Recherche expérimentale sur un nouveau système de chauffe-eau à pompe à chaleur aérothermique sans givre.

[In Chinese. / En chinois.]

Auteurs : WANG Z., WANG F., ZHENG Y.

Type d'article : Article

Résumé

Aiming to the frosting problem of air-source heat pump (ASHP) at low temperatures, a novel frost-free air-source heat pump water heater (ASHPWH) system is proposed in the paper,in which dehumidilication of solid desiccant is used lo reduce the humidity ratios of ambient air to realize frost-free operation. In order to keep the system working continuously, phase-change thermal storage is used to recycle the condensation heat that acts as a low temperature resource to regenerate the solid desiccant. The novel system was compared experimentally with conventional defrost system at a temperature of 0°C and relative humidity (RH) of 80%. The results show that the average COP of the system was increased by 7.25% and 46.3% in comparison with hot-gas bypass defrosting and electric resistance heating, which proves the feasibility of the novel system.

Documents disponibles

Format PDF

Pages : 52-58

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails


Liens


Voir d'autres articles du même numéro (6)
Voir la source