Réduction de la circulation d'air pendant le conditionnement d'air.

Hospodárnost cirkulace vzduchu pri klimatizaci.

Auteurs : HEMZAL K.

Type d'article : Article

Résumé

Central air-conditioning equipment, taking out heat gains merely by the air, are often designed with a partial circulation of reversing (recuperative) air. The conception that the reversal heat gain is achieved by such an action is disproved in the contribution and it is evidenced in the example that circulation is more demanding from the energy point of view than treatment of the ventilating air, only. It is stated therein that the volume of circulation during an extreme summer is decided by maximally allowable under-cooling of the distributed air limited with the dimensioning of the outlets. Efficiencies of methods using the reverse air as concerns rotational recovery heat exchangers installed in front of and behind the exchanger, are compared in the second part of the contribution.

Documents disponibles

Format PDF

Pages : pp. 66-70

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Hospodárnost cirkulace vzduchu pri klimatizaci.
  • Identifiant de la fiche : 2010-1549
  • Langues : Tchèque
  • Source : Vytápení Vetrání Instalace - vol. 19 - n. 2
  • Date d'édition : 2010

Liens


Voir d'autres articles du même numéro (2)
Voir la source