REGULATION DES ECHANGEURS REFROIDISSEURS A AIR.

CONTROL OF AIR COOLING COILS.

Auteurs : AHERN W. R.

Type d'article : Article

Résumé

LA REGULATION A UN NIVEAU (PAR TOUT OU RIEN) EXIGE QUE LES RECHAUFFEURS A RETROACTION PROPORTIONNELLE ET INTEGRALE SOIENT CONVENABLEMENT APPLIQUES DANS LE THERMOSTAT. LA COMMUTATION A PLUSIEURS NIVEAUX DES ECHANGEURS EXIGE QUE LE NIVEAU DE PUISSANCE MINIMALE NE DEPASSE PAS 25 % DU TOTAL. LA REGULATION PAR ETRANGLEMENT DU DEBIT D'EAU DE REFROIDISSEMENT EXIGE UN EFFORT MAXIMAL POUR LINEARISER LA REPONSE ET L'UTILISATION DE LA REGULATION A REPONSE PROPORTIONNELLE ET INTEGRALE AVEC UNE LARGE BANDE PROPORTIONNELLE. LA REGULATION PAR ETRANGLEMENT DU DEBIT D'AIR EXIGE DES REGISTRES BIEN CONCUS ET ROBUSTES. LES EVAPORATEURS A DETENTE DIRECTE DOIVENT ETRE DIVISES EN UN NOMBRE DE CIRCUITS TEL QU'ON AIT UNE GRANDE VITESSE DU FRIGORIGENE DEPUIS L'ENTREE JUSQU'AU-DELA DE L'EMPLACEMENT DU BULBE DU DETENDEUR THERMOSTATIQUE. IL FAUT ACCORDER UNE ATTENTION SPECIALE AUX EVAPORATEURS A DETENTE DIRECTE SOUMIS A UNE VITESSE D'AIR VARIABLE COMME C'EST LE CAS DANS LES INSTALLATIONS MULTIZONES.

Détails

  • Titre original : CONTROL OF AIR COOLING COILS.
  • Identifiant de la fiche : 1983-1736
  • Langues : Anglais
  • Source : Aust. Refrig. Air Cond. Heat. - vol. 36 - n. 10
  • Date d'édition : 10/1982
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.