Document IIF

Résistance de contact dans des condenseurs de conditionnement d'air à tubes et plaques-ailettes, refroidis par air.

Contact resistance in air-cooled plate fin-tube air-conditioning condensers.

Auteurs : CRITOPH R. E., HOLLAND M. K., TURNER L.

Type d'article : Article, Article de la RIF

Résumé

Test equipment and procedures are developed to measure the heat transfer performance of an industry-standard wavy plate fin-tube condenser, and to compare it with alternative designs. Two test rigs are employed: one uses direct electric heating, and the other uses an R22 thermosyphon. Analysis reveals that the standard production heat exchanger suffers from excessive fin-tube resistance. This is confirmed by sectioning and microscopic examination. Seven different designs are compared at the same Reynolds number. The results are analysed to isolate the air-side heat transfer coefficient.

Documents disponibles

Format PDF

Pages : 400-406

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Contact resistance in air-cooled plate fin-tube air-conditioning condensers.
  • Identifiant de la fiche : 1998-0838
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 19 - n. 6
  • Date d'édition : 07/1996

Liens


Voir d'autres articles du même numéro (6)
Voir la source