Résultats d'une étude expérimentale sur un réfrigérateur de pointe à pompe à jet fonctionnant au R-245fa.

Results of an experimental study of an advanced jet-pump refrigerator operating with R-245fa.

Auteurs : EAMES I. W., ABLWAIFA A. E., PETRENKO V.

Type d'article : Article

Résumé

An experimental jet-pump refrigeration system was designed and constructed to assess the performance of R-245fa (1,1,1,3,3-pentafluoropropane) as a suitable refrigerant. The paper describes and evaluates the results of experimental tests over a range of operating conditions. In addition, the effects of primary nozzle geometry on jet-pump performance are reported. Performance maps, useful for practical design and control are also provided. Experimental values of COP between 0.25 and 0.7 were obtained. These results demonstrate that low-grade heat can be used to drive efficient jet-pump refrigeration systems, using R-245fa as their working fluid, for high temperature applications, such air conditioning. [Reprinted with permission from Elsevier. Copyright, 2007].

Détails

  • Titre original : Results of an experimental study of an advanced jet-pump refrigerator operating with R-245fa.
  • Identifiant de la fiche : 2008-0655
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 27 - n. 17-18
  • Date d'édition : 12/2007

Liens


Voir d'autres articles du même numéro (1)