Résultats et perspective d'un cycle ammoniac-eau à forte élévation de température par rectification inversée.
Results and perspective of an ammonia-water cycle with high temperature lift using reverse rectification.
Auteurs : KAHN R., HUGO H., ALEFELD G.
Résumé
The COP of a conventional ammonia-water cycle can be significantly improved by a reverse rectification-column and a second absorber which is combined with a two-stage refrigerant expansion. At an internal temperature lift of 85 K (-20 to 65 deg C) these modifications result in a 50% higher COP for cooling-assuming ideal components. The proposed cycle with reverse rectification was realized in a laboratory test plant with a refrigeration capacity of 10 kilowatts at -20 deg C. This machine was operated at a solution temperature up to 225 deg C and a condenser pressure up to 3 megapascals. The authors measured the COP versus temperature lift and the load behaviour. A COP of 0.38 was achieved at a temperature lift of 85 K. Furthermore it will be discussed how the COP of a triple-effect plant can be improved by reverse rectification.
Détails
- Titre original : Results and perspective of an ammonia-water cycle with high temperature lift using reverse rectification.
- Identifiant de la fiche : 1998-0864
- Langues : Anglais
- Source : Ab-sorption 96. Towards sustainable technologies. Proceedings./ Ab-sorption 96. Vers les technologies durables. Comptes rendus.
- Date d'édition : 17/09/1996
- Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.
Liens
Voir d'autres communications du même compte rendu (115)
Voir le compte rendu de la conférence
Indexation
- Thèmes : Systèmes à absorption et adsorption
- Mots-clés : Banc d'essai; Rectification; Conception; Ammoniac-eau; Système à absorption; COP
-
Results and perspective of an ammonia-water cyc...
- Auteurs : KAHN R., HUGO H., ALEFELD G.
- Date : 03/09/1996
- Langues : Anglais
- Source : Applications for Natural Refrigerants
- Formats : PDF
Voir la fiche
-
Machine frigorifique à absorption à colonne de ...
- Auteurs : MINKUS B. A.
- Date : 1991
- Langues : Russe
- Source : Kholodilnaya Tekhnika - n. 12
Voir la fiche
-
Test rig for ammonia-based absorption chiller c...
- Auteurs : LECUONA A., ROA J., VENEGAS M., et al.
- Date : 19/04/2007
- Langues : Anglais
- Source : Ammonia Refrigeration Technology for Today and Tomorrow.
- Formats : PDF
Voir la fiche
-
Compact sieve-tray distillation column for ammo...
- Auteurs : ANAND G., ERICKSON D. C.
- Date : 1999
- Langues : Anglais
- Source : ASHRAE Transactions. 1999 Winter Meeting, Chicago, Illinois + CD-ROM.
Voir la fiche
-
Analyse de la performance du cycle d'absorption...
- Auteurs : TSUJIMORI A., OZAKI E.
- Date : 1996
- Langues : Japonais
- Source : Trans. JAR - vol. 13 - n. 1
Voir la fiche