Document IIF

Rétention du condensat sur un refroidisseur d'air du type tube aileté.

Condensate retention on a louver-fin-and-tube air-cooling coil.

Auteurs : XU X., LEUNG C., CHAN M., et al.

Type d'article : Article, Article de la RIF

Résumé

This paper presents a study of condensate retention on a louver-fin-and-tube air cooling coil, which is commonly used in air conditioning systems. Compared to previously related work focusing on the influence of condensate retention on the heat and mass transfer between air and a cooling coil, the present study emphasizes the impacts of operating parameters on condensate retention on a cooling coil. A new method to describe the steady-state condensation has been suggested and a new mathematical model to represent the force balance of retained condensate developed. The mass of condensate retained has been measured experimentally under various operating conditions of a direct expansion air-cooling and dehumidification system. The influences of air dry-bulb temperature, moisture content and Reynolds Number on condensate retention are discussed. The model developed relates the mass of condensate retained to condensing rate, and is successful in predicting the trends of condensate retention under normal operating conditions for air cooling applications.

Documents disponibles

Format PDF

Pages : 409-417

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Condensate retention on a louver-fin-and-tube air-cooling coil.
  • Identifiant de la fiche : 2007-0790
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 30 - n. 3
  • Date d'édition : 05/2007

Liens


Voir d'autres articles du même numéro (16)
Voir la source