S’approcher de la haute pression optimale grâce à la gestion de la charge en frigorigène d’un chauffe-eau à pompe à chaleur au CO2 transcritique.
Approaching optimal high pressure by charge management in transcritical CO2 heat pump water heater.
Numéro : No 117
Auteurs : HE Y. J., LIANG X. Y., CHENG J. H., SHAO L. L., ZHANG C. L.
Résumé
Transcritical CO2 cycle has been widely applied in heat pump systems. Optimal high pressure is crucial to the performance of transcritical CO2 heat pump water heater (HPWH). However, current techniques for high pressure control cannot meet the requirements of easy-to-implement and low COP loss simultaneously. From the perspective of charge management, this work aims to approach optimal high pressure in CO2 HPWH without high pressure control. By modeling a running CO2 HPWH, we in-depth investigated the relationship between optimal high pressure and refrigerant charge. It was found that for practical systems, the essence of optimal high pressure control is to manage optimum refrigerant charge of the system. If the optimum charge of the system remains constant under any working conditions, the system can be guaranteed at optimal high pressure with fixed refrigerant charge. Then the influence of water inlet temperature, water outlet temperature and ambient temperature on optimum refrigerant charge was analyzed. Two system design methods with the aim of minimizing the change of optimum charge under different working conditions are presented, which are re-sizing heat exchangers and adding additional refrigerant reservoir. The minimum average COP loss of the redesigned system can be reduced to only 2.82% and 0.67%, respectively.
Documents disponibles
Format PDF
Pages : 13 p.
Disponible
Gratuit
Détails
- Titre original : Approaching optimal high pressure by charge management in transcritical CO2 heat pump water heater.
- Identifiant de la fiche : 30029992
- Langues : Anglais
- Sujet : Technologie
- Source : 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
- Date d'édition : 31/08/2021
Liens
Voir d'autres communications du même compte rendu (198)
Voir le compte rendu de la conférence
Indexation
-
Approaching optimum COP by refrigerant charge m...
- Auteurs : HE Y. J., LIANG X. Y., CHENG J. H., SHAO L. L., ZHANG C. L.
- Date : 10/2020
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 118
- Formats : PDF
Voir la fiche
-
Optimal heat rejection pressure of CO2 heat pum...
- Auteurs : CHEN Y. G.
- Date : 10/2019
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 106
- Formats : PDF
Voir la fiche
-
The role of internal heat exchanger in an R744 ...
- Auteurs : CERNICIN V., ZHANG W., HRNJAK P.
- Date : 10/07/2022
- Langues : Anglais
- Source : 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Evaluation of existing refrigerant charge deter...
- Auteurs : JOUNAY M., CAURET O., TEUILLIERES C., TRAN C. T.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche
-
A universal refrigerant charge fault detection ...
- Auteurs : LI Z., WELCH D., SHEN B., GLUESENKAMP K., BUTLER B., MORGAN S.
- Date : 2022
- Langues : Anglais
- Source : 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche