Document IIF

Simulation des cycles frigorifiques à absorption à ammoniac-eau-sel.

Simulation of ternary ammonia-water-salt absorption refrigeration cycles.

Auteurs : BALAMURU V. G., IBRAHIM O. M., BARNETT S. M.

Type d'article : Article, Article de la RIF

Résumé

This paper proposes a new working fluid for refrigeration cycles utilizing low temperature heat sources. The proposed working fluid consists of the ammonia-water working fluid mixture and a salt. The salt is used to aid the removal of ammonia from the liquid solution. This effect is a manifestation of the well known "salting-out" effect. While the addition of salt improves the generator performance, it also has a detrimental effect on the absorber. The overall effects on the performance of three absorption cycles using the NH3-H2O-NaOH working fluid have been investigated using computer simulations. The results indicated that salting out can lower the generator operating temperature while simultaneously improving the cycle performance. Furthermore, limiting the salt to the generator suggests potential for further improvement in cycle performance.

Documents disponibles

Format PDF

Pages : 31-42

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Simulation of ternary ammonia-water-salt absorption refrigeration cycles.
  • Identifiant de la fiche : 2000-0733
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 23 - n. 1
  • Date d'édition : 01/2000

Liens


Voir d'autres articles du même numéro (5)
Voir la source