Résumé
The model presented includes sub-models for key components, such as a non-economized compressor, an economized compressor, a shell-and-tube condenser, an expansion valve, and a flooded evaporator. A sequential modular method and successive substitution methods were combined together to carry out the simulation of the chillers. It was found that the cooling capacity of a screw liquid chiller appears to be increased by adding the economizer, but only when the volumetric ratio of the first stage internal compression is greater than a certain value; the economized screw liquid chiller can gain a higher COP than that of the non-economized one.
Détails
- Titre original : Steady-state simulation of screw liquid chillers.
- Identifiant de la fiche : 2003-2990
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 22 - n. 15
- Date d'édition : 10/2002
Liens
Voir d'autres articles du même numéro (2)
Voir la source
Indexation