Stratégie de fonctionnement de systèmes de pompe à chaleur géothermiques solaires.

[In Chinese. / En chinois.]

Auteurs : WANG E., HE F., QI C.

Type d'article : Article

Résumé

A solar-ground source heat pump system model according to the climatic conditions in Tianjin is established. A simulation study of the system based on TRNSYS program is carried out, the energy consumption of the system and the ground temperature change are analysed, and the operation strategy is studied with emphasis. An appropriate operation strategy based on the coefficient of performance (COP) of system is selected, i.e. to turn on the solar collection pump as the temperature difference between collector outlet and tank outlet is higher than 15°C, and to turn off the pump until it is under 2°C, and to turn on the solar storage pump when tank outlet temperature is higher than 50°C, and to turn it off until the temperature difference between inlet and outlet of the borehole heat exchanger is under 5°C.

Documents disponibles

Format PDF

Pages : 83-87

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 30009412
  • Langues : Chinois
  • Source : HV & AC - vol. 42 - n. 272
  • Date d'édition : 12/2012

Liens