Transfert de chaleur à partir de la sortie de l'évaporateur vers le train thermostatique des détendeurs thermostatiques.

Heat transfer from the evaporator outlet to the charge of thermostatic expansion valves.

Résumé

In this paper, a model for the overall heat transfer between the pipe and the charge is presented. Geometrical data and material properties have been kept as parameters in order to be able to see the effect of changes in those. Some of the parameters (e.g. thermal contact resistances) have been determined by a finite element model and a series of experiments. The model has been validated using test results obtained under different operating conditions and has been found to predict the time constant for the temperature development in the bulb within 1-10%. Furthermore, it has been found that approximately 20% of the heat transfer takes place trough the mounting strap.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Heat transfer from the evaporator outlet to the charge of thermostatic expansion valves.
  • Identifiant de la fiche : 2008-2105
  • Langues : Anglais
  • Source : 2006 Purdue Conferences. 18th International Compressor Engineering Conference at Purdue & 11th International Refrigeration and Air-Conditioning Conference at Purdue [CD-ROM].
  • Date d'édition : 17/07/2006

Liens


Voir d'autres communications du même compte rendu (157)
Voir le compte rendu de la conférence