Transfert de chaleur et d'humidité dans un échangeur de chaleur avec une roue de séchage déshydratante. 2. Validation et études de sensibilité.

Heat and moisture transfer in desiccant coated rotary energy exchangers. 2. Validation and sensitivity studies.

Auteurs : SIMONSON C. J., BESANT R. W.

Type d'article : Article

Résumé

Neglecting thermal and moisture storage in the air is shown to result in errors as large as 2.4% in the predicted effectiveness of a rotary energy exchanger at typical wheel speeds. Including the heat of sorption in the model affects the predicted effectiveness only slightly. However, the predicted effectiveness is greatly affected by whether the heat of phase change is assumed to remain in the air or in the matrix. Controlling the energy rate of the energy exchanger by controlling wheel speed may be impractical because the sensitivity of each effectiveness to wheel speed differs with each operating condition. The model is also used to show the importance of the entry length and thermal conductivity on the predicted performance of rotary energy exchangers.

Détails

  • Titre original : Heat and moisture transfer in desiccant coated rotary energy exchangers. 2. Validation and sensitivity studies.
  • Identifiant de la fiche : 1998-3790
  • Langues : Anglais
  • Source : HVAC&R Research - vol. 3 - n. 4
  • Date d'édition : 10/1997
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (3)
Voir la source