Transfert de chaleur lors de la condensation et chute de pression de HFC-134a dans un échangeur de chaleur hélicoîdal à double tube.

Condensation heat transfer and pressure drop of HFC-134a in a helically coiled concentric tube-in-tube heat exchanger.

Auteurs : WONGWISES S., POLSONGKRAM M.

Type d'article : Article

Résumé

The two-phase heat transfer coefficient and pressure drop of pure HFC-134a condensing inside a smooth helically coiled concentric tube-in-tube heat exchanger are experimentally investigated. The test section is a 5.786 m long helically coiled double tube with refrigerant flowing in the inner tube and cooling water flowing in the annulus. The inner tube is made from smooth copper tubing of 9.52-mm outer diameter and 8.3-mm inner diameter. The outer tube is made from smooth copper tubing of 23.2 mm outer diameter and 21.2 mm inner diameter. The heat exchanger is fabricated by bending a straight copper double-concentric tube into a helical coil of six turns. The diameter of coil is 305 mm. The pitch of coil is 35 mm. The test runs are done at average saturation condensing temperatures ranging between 40 and 50°C. The mass fluxes are between 400 and 800 kg m2/s and the heat fluxes are between 5 and 10 kW/m2. The pressure drop across the test section is directly measured by a differential pressure transducer. The quality of the refrigerant in the test section is calculated using the temperature and pressure obtained from the experiment. The average heat transfer coefficient of the refrigerant is determined by applying an energy balance based on the energy rejected from the test section. The effects of heat flux, mass flux and, condensation temperature on the heat transfer coefficients and pressure drop are also discussed. It is found that the percentage increase of the average heat transfer coefficient and the pressure drop of the helically coiled concentric tube-in-tube heat exchanger, compared with that of the straight tube-in-tube heat exchanger, are in the range of 33-53 and 29-46%, respectively. New correlations for the condensation heat transfer coefficient and pressure drop are proposed for practical applications. [Reprinted with permission from Elsevier. Copyright, 2006].

Détails

  • Titre original : Condensation heat transfer and pressure drop of HFC-134a in a helically coiled concentric tube-in-tube heat exchanger.
  • Identifiant de la fiche : 2007-0549
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 49 - n. 23-24
  • Date d'édition : 11/2006

Liens


Voir d'autres articles du même numéro (2)
Voir la source