Document IIF

Transfert de chaleur vers un frigorigène circulant dans un tube d'un diamètre de 1 mm.

Two-phase heat transfer to a refrigerant in a 1 mm diameter tube.

Auteurs : LIN S., KEW P. A., CORNWELL K.

Type d'article : Article, Article de la RIF

Résumé

A study of two-phase flow and heat transfer in a small tube of 1 mm internal diameter has been conducted experimentally as part of a wider study of boiling in small channels. R141b has been used as the working fluid. The boiling heat transfer in the small tube has been measured over a mass flux range of 300-2000 kg/m2 and heat flux range of 10-1150 kW/m2. In this paper the boiling map for a mass velocity of 510 kg/m2 and heat flux of 18-72 kW/m2 is discussed and the problems of determining heat transfer coefficients in small channels are highlighted.

Documents disponibles

Format PDF

Pages : 51-56

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Two-phase heat transfer to a refrigerant in a 1 mm diameter tube.
  • Identifiant de la fiche : 2001-1750
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 24 - n. 1
  • Date d'édition : 01/2001

Liens


Voir d'autres articles du même numéro (9)
Voir la source