TRANSFERT THERMIQUE DANS UN THERMOSIPHON BIPHASIQUE OPERANT AVEC UN FLUIDE PROCHE DE L'ETAT CRITIQUE.

HEAT TRANSFER IN A TWO-PHASE THERMOSYPHON OPERATING WITH A FLUID IN THE NEAR CRITICAL STATE.

Auteurs : GROSS U., HAHNE E.

Type d'article : Article

Résumé

ON ETUDIE EXPERIMENTALEMENT LE TRANSFERT THERMIQUE DANS LES ZONES DE REFROIDISSEMENT ET DE RECHAUFFEMENT D'UN THERMOSIPHON FERME. LE R115 EST UTILISE COMME FLUIDE DE TRAVAIL. LA QUANTITE DE FLUIDE EST DETERMINEE EN TENANT COMPTE DU VOLUME MASSIQUE CRITIQUE. SELON LA PRESSION, IL Y A TROIS REGIMES D'EBULLITION : EBULLITION NUCLEEE, EBULLITION NUCLEEE EN REGIME DE TRANSITION ET L'EBULLITION PELLICULAIRE. DANS LE THERMOSIPHON, IL EXISTE LA CONDENSATION EN PELLICULE LAMINAIRE OU TURBULENTE. LE TRANSFERT THERMIQUE COUPLE DANS LES ZONES DE CHAUFFAGE ET DE REFROIDISSEMENT CAUSE UN FONCTIONNEMENT GLOBAL AVEC DES CONDITIONS OPTIMALES POUR UN ANGLE D'INCLINAISON DE 40 DEG ENVIRON ET UN FLUX THERMIQUE ET DES PRESSIONS FAIBLES.

Détails

  • Titre original : HEAT TRANSFER IN A TWO-PHASE THERMOSYPHON OPERATING WITH A FLUID IN THE NEAR CRITICAL STATE.
  • Identifiant de la fiche : 1986-0107
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 28 - n. 3
  • Date d'édition : 1985

Liens


Voir d'autres articles du même numéro (6)
Voir la source