Transformateur de chaleur à absorption biétagé et en parallèle au TFE-H2O-E181, un fluide actif ternaire.

Double-lift parallel mode absorption heat transformer with the ternary working fluid TFE-H2O-E181.

Auteurs : XU S. M., ZHANG L.

Résumé

The paper gives thermal property expression formulae of 2,2,2-trifluoroethanol (TFE)-water (H2O)-tetraethylene glycol dimethyl ether (TEGDME or E181), which can be used for absorption heat transformer as ternary working fluid. The double-lift parallel mode absorption heat transformer using TFE-H2O-E181 as working fluid is proposed in order to upgrade low-temperature level heat energy to a high level and recover more heat energy in low-temperature level waste heat. The temperature of the available waste heat can drop nearly to 40°C while cooling water is 28°C, which takes the cost of reducing the COP of the heat transformer.

Détails

  • Titre original : Double-lift parallel mode absorption heat transformer with the ternary working fluid TFE-H2O-E181.
  • Identifiant de la fiche : 2006-2347
  • Langues : Anglais
  • Source : Cryogenics and refrigeration. Proceedings of ICCR 2003.
  • Date d'édition : 22/04/2003

Liens


Voir d'autres communications du même compte rendu (166)
Voir le compte rendu de la conférence