UN AUTRE ASPECT DES MODES DE COMMANDE DES CONDITIONNEURS D'AIR : INFLUENCE SUR L'HUMIDITE INTERIEURE.

ANOTHER ASPECT OF DUTY CYCLING: EFFECTS ON INDOOR HUMIDITY.

Résumé

DES MESURES DE L'ELIMINATION DE CONDENSAT PROVENANT DU CONDITIONNEUR D'AIR AINSI QUE DE LA PERFORMANCE DE REFROIDISSEMENT DE CHALEUR SENSIBLE ET LATENTE TRANSITOIRE AU COURS DES OPERATIONS DE FONCTIONNEMENT INTERMITTENT ONT MONTRE QUE L'EXTRACTION NETTE D'HUMIDITE DIMINUAIT LORSQUE LE VENTILATEUR FONCTIONNAIT CONTINUELLEMENT. LA PERFORMANCE MOYENNE D'EXTRACTION D'HUMIDITE ETAIT RELATIVEMENT INDEPENDANTE DE LA FRACTION DE TEMPS DE FONCTIONNEMENT DU COMPRESSEUR DANS LE MODE AUTOMATIQUE DU VENTILATEUR MAIS VARIAIT NETTEMENT DANS LE MODE DE < MARCHE PERMANENTE > DU VENTILATEUR. LE TAUX DE RE-EVAPORATION AUGMENTAIT EN FONCTION DU NOMBRE DE CYCLES. LE NIVEAU D'HUMIDITE INTERIEUR ETAIT SUPERIEUR DANS LE CAS DU MODE DE < MARCHE PERMANENTE > DU VENTILATEUR PAR RAPPORT AU MODE AUTOMATIQUE. LA PLUPART DES DISPOSITIFS DE COMMANDE DES CONDITIONNEURS D'AIR, LAISSANT LA VENTILATION INTERIEURE FONCTIONNER APRES L'ARRET DU COMPRESSEUR, REEVAPORERONT UNE PARTIE DE L'HUMIDITE CONDENSEE.

Détails

  • Titre original : ANOTHER ASPECT OF DUTY CYCLING: EFFECTS ON INDOOR HUMIDITY.
  • Identifiant de la fiche : 1988-0273
  • Langues : Anglais
  • Date d'édition : 1987
  • Source : Source : ASHRAE Trans.
    vol. 93; n. 1; 1678-1687; 7 fig.; 2 tabl.; 2 ref.