UN MODELE SIMPLIFIE POUR L'ABSORPTION DE VAPEURS DANS DES PELLICULES DE LIQUIDE S'ECOULANT AU-DESSUS DE TUBES HORIZONTAUX REFROIDIS.

A SIMPLIFIED MODEL FOR ABSORPTION OF VAPOURS INTO LIQUID FILMS FLOWING OVER COOLED HORIZONTAL TUBES.

Résumé

ON PRESENTE UNE ANALYSE DE L'ABSORPTION D'UNE VAPEUR DANS UNE PELLICULE DE LIQUIDE S'ECOULANT AU-DESSUS D'UN TUBE HORIZONTAL REFROIDI, CONFIGURATION COURANTE POUR LES REFROIDISSEURS A ABSORPTION. ON UTILISE DES HYPOTHESES AU SUJET DE LA COUCHE LIMITE POUR LE TRANSPORT DE LA QUANTITE DE MOUVEMENT, L'ENERGIE ET L'ESPECE DANS UNE PELLICULE DE LIQUIDE LAMINAIRE SUPPOSEE. ON UTILISE DES SOLUTIONS DE SIMILITUDE POUR RESOUDRE LE TRANSPORT DE QUANTITE DE MOUVEMENT ET D'ENERGIE. LE PROCESSUS EST MODELISE NUMERIQUEMENT. LES RESULTATS POUR L'EAU-BROMURE DE LITHIUM SONT COMPARES AVEC UN MODELE DETAILLE PLUS ANCIEN AINSI QU'AVEC LES PROPRIETES RELEVEES DANS DES GROUPES REFROIDISSEURS A ABSORPTION EN FONCTIONNEMENT.

Détails

  • Titre original : A SIMPLIFIED MODEL FOR ABSORPTION OF VAPOURS INTO LIQUID FILMS FLOWING OVER COOLED HORIZONTAL TUBES.
  • Identifiant de la fiche : 1988-2280
  • Langues : Anglais
  • Date d'édition : 1987
  • Source : Source : ASHRAE Trans.
    vol. 93; n. 2; 2454-2466; 3 fig.; 3 tabl.; 16 ref.