The solution has been studied to recover energy from the exhaust air of a ventilation system in a new building of the Hospital Sant’Orsola-Malpighi in Bologna. The new structure, with a total area of 24 000 m2, 13 operating theaters, 22 beds for intensive care unit, a 1000 m2 large Central Sterile Supply Department, 17 rooms for imaging and the new Emergency Department, has a ventilation system that handles 240 000 m3/h of external air. Because of the particular application every kind of contamination between the fresh and the exhaust air must be avoided and so the air is handled by four air handling units (AHU) and four extractors with no physical connection. Considering the quantity of air handled every hour, the importance of recovering energy from the exhaust air is evident and the classic scheme with an air/water coil on the extractor, an hydraulic circuit with a circulation pump and another air/water coil on the AHU was considered unsatisfactory. A water/water reversible heat pump (HP) has been placed between the two air/water coils and two different hydraulic circuits have been created to connect the primary circuit of the HP with the AHUs and the secondary one with the air extractors (AE).
Documents disponibles
Format PDF
Pages : 151-159
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : An “active” recovery system for air handling units.
- Identifiant de la fiche : 30001147
- Langues : Anglais
- Source : Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Date d'édition : 05/04/2011
Liens
Voir d'autres communications du même compte rendu (122)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Conditionnement d'air pour le confort;
Conditionnement d’air dans les laboratoires et l’industrie;
Autres applications des pompes à chaleur;
Autres systèmes à économie / récupération d'énergie - Mots-clés : Hiver; Air extrait; Ventilation; Récuperation de chaleur; Pompe à chaleur; Hôpital; Conditionnement d'air; Chauffage; Eau-eau
-
Knowledge from running of air conditioning in c...
- Auteurs : RUBINOVÁ O.
- Date : 10/06/2007
- Langues : Anglais
- Source : Clima 2007. WellBeing Indoors. Proceedings of the 9th REHVA World Congress [CD-ROM + Abstract book].
Voir la fiche
-
Info-dex: 2012-2013 directories.
- Date : 06/2012
- Langues : Anglais
Voir la fiche
-
Info-dex: 2011-2012 directories.
- Date : 06/2011
- Langues : Anglais
Voir la fiche
-
Commissioning of hospitals for occupant health ...
- Auteurs : O'BRIEN GIBBONS J., VILLANI J. D.
- Date : 16/06/2013
- Langues : Anglais
- Source : Clima 2013. 11th REHVA World Congress and 8th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings.
- Formats : PDF
Voir la fiche
-
SYSTEMES DE CONDITIONNEMENT D'AIR AVEC UTILISAT...
- Auteurs : IBRAGIMOVA L. R.
- Date : 1986
- Langues : Russe
- Source : Kholodilnaya Tekhnika - n. 6
Voir la fiche