Document IIF
Une analyse alternative appliquée pour étudier la performance de l'éjecteur utilisé dans un système frigorifique de pompe à jet au R141b.
An alternative analysis applied to investigate the ejector performance used in R141b jet-pump refrigeration system.
Auteurs : THONGTIP T., APHORNRATANA S.
Type d'article : Article, Article de la RIF
Résumé
The system performance of R141b jet-pump refrigerator is discussed based on an alternative analysis. It explains the operation of the jet-pump refrigerator operating under actual conditions. A 2 kW cooling of R141b jet-pump refrigerator is designed and constructed to test the ejector performance. With the use of an alternative analysis, point of interest called “critical evaporator temperature” is determined. This point indicates the lowest possible evaporator temperature where the secondary fluid flow is still choked. The critical point varies with the change in operating conditions and with the primary nozzle used. An increase of primary mass flow rate causes the critical point reducing. However, it does not always true. When the primary mass flow rate increases to a certain value, the refrigerator is operated at higher critical evaporator temperature. Thus, the optimum range of the primary mass flow rate for this particular ejector is provided for this present work.
Documents disponibles
Format PDF
Pages : 20-33
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : An alternative analysis applied to investigate the ejector performance used in R141b jet-pump refrigeration system.
- Identifiant de la fiche : 30014038
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 53
- Date d'édition : 05/2015
Liens
Voir d'autres articles du même numéro (18)
Voir la source
Indexation
-
Joint research on ejector cooling technology.
- Auteurs : HUANG B. J., CHANG J. M., PETRENKO V. A., et al.
- Date : 2001
- Langues : Anglais
- Source : Non-compression refrigeration and cooling. Proceedings of the Second International Workshop.
Voir la fiche
-
Comparaison des paramètres expérimentaux et cal...
- Auteurs : PETRENKO V. A., VOLOVIK A. S.
- Date : 2006
- Langues : Russe
- Source : Holodil'na Tehnika i Tehnologiâ - n. 6
Voir la fiche
-
A 1-D analysis of ejector performance.
- Auteurs : HUANG B. J., CHANG J. M., WANG C. P., et al.
- Date : 08/1999
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 22 - n. 5
- Formats : PDF
Voir la fiche
-
Performance of ejector cooling system with ther...
- Auteurs : WANG J. H., WU J. H., HU S. S., et al.
- Date : 07/2009
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 29 - n. 10
Voir la fiche
-
Recherches théoriques sur un système frigorifiq...
- Auteurs : PETRENKO V. A., KIRILLOV V. H., VOLOVIK A. S.
- Date : 2006
- Langues : Russe
- Source : Holodil'na Tehnika i Tehnologiâ - n. 2
Voir la fiche