Document IIF

Une étude des fuites de frigorigène en froid commercial.

An investigation of refrigerant leakage in commercial refrigeration.

Auteurs : FRANCIS C., MAIDMENT G., DAVIES G.

Type d'article : Article, Article de la RIF

Résumé

Given that refrigerant demand is set to rapidly increase, long term solutions for leakage prevention are required to affect change in the industry. This paper presents the results of a project which investigated refrigerant leakage within two of the UK's major supermarket chains. Leakage data from 1464 maintenance records were analyzed. The analysis categorized the type, location of each leak and volume of refrigerant replaced during repair. Over 82% of the recorded leaks were from R404A refrigeration systems, and mainly consisted of pipe or joint failures or a leaking seal/gland/core located in the compressor pack and the high pressure liquid line. It is recommended that the industry focuses on improving design, installation and maintenance of pipework and valves, at the components that most often develop faults to minimize refrigerant leakage.

Documents disponibles

Format PDF

Pages : 10-19

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : An investigation of refrigerant leakage in commercial refrigeration.
  • Identifiant de la fiche : 30019965
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 74
  • Date d'édition : 02/2017

Liens


Voir d'autres articles du même numéro (56)
Voir la source