Utilisation d'une surface intérieure à rainures croisées pour améliorer les caractéristiques de transfert de chaleur à l'intérieur de tubes horizontaux pour un frigorigène zéotropique. 2. Essai d'évaporation.

[In Japanese. / En japonais.]

Auteurs : UCHIDA M., ITOH M., SHIKAZONO N.

Type d'article : Article

Résumé

The evaporation of a zeotropic refrigerant (R407C) inside horizontal tubes was investigated experimentally using two types of new cross-grooved tubes and a conventional single-grooved tube. At low mass flows, the improved cross-grooved tube showed higher evaporative heat transfer coefficients than the single-grooved tube, but at higher mass flows the single-grooved tube showed higher heat transfer coefficients. The pressure drop of the cross-grooved tube was greater than that of the improved cross-grooved tube (see also Bulletin of the IIR, ref. 2000-2887).

Détails

  • Titre original : [In Japanese. / En japonais.]
  • Identifiant de la fiche : 2003-2205
  • Langues : Japonais
  • Source : Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 19 - n. 1
  • Date d'édition : 2002
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (9)
Voir la source