UTILISATION DE MELANGES DE FRIGORIGENES DANS LES POMPES A CHALEUR AIR-AIR.

THE USE OF MIXED REFRIGERANTS IN AIR TO AIR HEAT PUMPS.

Auteurs : COOPER W. D.

Résumé

AVEC DES MELANGES D'UN FRIGORIGENE A POINT D'EBULLITION ELEVE ET D'UN FRIGORIGENE A BAS POINT D'EBULLITION, ON PEUT AUGMENTER LA MASSE VOLUMIQUE DE LA VAPEUR A L'ASPIRATION ET LA PUISSANCE DU COMPRESSEUR EN RETIRANT UNE PARTIE DES BOUILLEURS HAUTE TEMPERATURE DU CIRCUIT ACTIF. ON Y ARRIVE EN UTILISANT L'ACCUMULATEUR COMME APPAREIL DE DISTILLATION A UN PLATEAU. LE LIQUIDE ACCUMULE EST PLUS RICHE DANS LE BOUILLEUR A HAUTE TEMPERATURE, ET LA FRACTION DE SOLUTION EN CIRCULATION EST PLUS RICHE DANS LE BOUILLEUR A BASSE TEMPERATURE QUE LA COMPOSITION CHARGEE. DANS LES ESSAIS SUR DES POMPES A CHALEUR A PLUSIEURS BLOCS AVEC UN MELANGE DE R13 B1 ET DE R152 A ON A AUGMENTE LA PUISSANCE THERMIQUE JUSQU'A 50 % PAR RAPPORT A LA PUISSANCE AVEC UTILISATION DE R22 LORSQUE LA TEMPERATURE DE LA SOURCE DE CHALEUR ETAIT DE 255 K (-18 DEG C). A TEMPERATURE ELEVEE DE LA SOURCE DE CHALEUR LA PERFORMANCE DE LA POMPE A CHALEUR AVEC DU R13 B1 ET DU R152 A E LA POMPE A R22.

Détails

  • Titre original : THE USE OF MIXED REFRIGERANTS IN AIR TO AIR HEAT PUMPS.
  • Identifiant de la fiche : 1984-1611
  • Langues : Anglais
  • Date d'édition : 1982
  • Source : Source : ASHRAE Trans.
    vol. 88; n. 1; 1159-1169; 3 fig.; 7 tabl.; 7 ref.; discuss.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.