VALIDATION A L'AIDE D'UNE CABINE D'ESSAI D'UN MICRO-ORDINATEUR POUR LA PREVISION DES TEMPERATURES ET LA REGULATION DES SYSTEMES DE CHAUFFAGE, VENTILATION ET CONDITIONNEMENT D'AIR.

TEST HUT VALIDATION OF A MICROCOMPUTER PREDICTIVE HVAC CONTROL.

Résumé

LES SYSTEMES DE REGULATION NORMAUX DE CHAUFFAGE, VENTILATION ET CONDITIONNEMENT D'AIR EVITENT QU'UN BATIMENT NE CONSTITUE UNE ACCUMULATION THERMIQUE POUR LE REFROIDISSEMENT PAR VENTILATEUR PENDANT LA NUIT OU LE GAIN DE CHALEUR INTERIEURE, EN MAINTENANT LA MACONNERIE A UNE TEMPERATURE CONSTANTE. UNE OSCILLATION DIURNEDE 4 K (4 DEG C) DE LA TEMPERATURE DE LA PIECE PENDANT LE JOUR A PEU D'INFLUENCE SUR LE CONFORT MAIS PERMET DES ECONOMIES CONSIDERABLES. ON A MIS AU POINT UN DISPOSITIF DE REGULATION A MICRO-ORDINATEUR QUI ETABLIT DE TELLES OSCILLATIONS DE TEMPERATURE ET ON A VERIFIE SA VALIDITE PENDANT 18 MOIS DANS UNE CABINE D'ESSAI SURVEILLEE AUTOMATIQUEMENT. UN BON NIVEAU DE CONFORT A ETE MAINTENU. AU COURS DE CERTAINES NUITS, UN PREREFROIDISSEMENT TROP IMPORTANT PAR VENTILATEUR POUVAIT ENTRAINER UN SURPLUS DE CHAUFFAGE LES LENDEMAINS. ON A ELIMINE CE GASPILLAGE A L'AIDE D'UN CALCUL UTILISANT LES TEMPERATURES INTERIEURES ET EXTERIEURES, PREVUES 24 HEURES A L'AVANCE.

Détails

  • Titre original : TEST HUT VALIDATION OF A MICROCOMPUTER PREDICTIVE HVAC CONTROL.
  • Identifiant de la fiche : 1989-1534
  • Langues : Anglais
  • Date d'édition : 1988
  • Source : Source : ASHRAE Trans.
    vol. 94; n. 1; 644-663; 11 fig.; 5 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.