ANALYSE D'UN SYSTEME COMMERCIAL D'ACCUMULATION DE GLACE : PRINCIPES DE CONCEPTION ET PERFORMANCE MESUREE.

ANALYSIS OF A COMMERCIAL ICE-STORAGE SYSTEM: DESIGN PRINCIPLES AND MEASURED PERFORMANCE.

Auteurs : PIETTE M. A.

Type d'article : Article

Résumé

ON RESUME L'ANALYSE DE LA MESURE DE LA PERFORMANCE D'UN SYSTEME D'ACCUMULATION DE GLACE, DANS UN GRAND IMMEUBLE DE BUREAUX A SAN FRANCISCO. LE SYSTEME D'ACCUMULATION PARTIELLE A ETE INSTALLE A UN COUT INFERIEUR A CELUI D'UN SYSTEME DE REFROIDISSEMENT TRADITIONNEL. L'ANALYSE DE LA CONCEPTION AVAIT PERMIS DE CONCLURE QU'EN REDUISANT LA DEMANDE DE POINTE EN ELECTRICITE -EN OPTANT POUR UN FONCTIONNEMENT NOCTURNE -, LE SYSTEME PERMETTRAIT D'ECONOMISER ENVIRON 38.000 DOLLARS PAR AN. AU COURS DE 1987, CEPENDANT, LES ECONOMIES N'ONT ETE QUE D'ENVIRON 10 % DE CETTE ESTIMATION SOIT 4.000 DOLLARS, A CAUSE DE L'INCAPACITE DU SYSTEME A DELIVRER LA CHARGE CALORIFIQUE REQUISE ET A CAUSE D'UN FONCTIONNEMENT ET D'UNE MAINTENANCE INSATISFAISANTS. (INT. BUILD. SERV. ABSTR., GB., 25, N 6, 1990/11-12, 90-01749.