In the paper, several innovative absorption cycles are evaluated in a wide range of operative conditions to estimate their real performances by assuming suitable efficiency for each heat exchange. The innovative cycles based on water-lithium bromide solution give the best performance (COP around 3 using a triple-effect heat pump), but they involve high temperature at the generator (up to 210 °C) with great corrosion or crystallisation problems. Innovative cycles based on ammonia-water solution give lower performances.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Analysis of high performance cycles for absorption heat pumps.
  • Identifiant de la fiche : 2000-1573
  • Langues : Anglais
  • Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Date d'édition : 19/09/1999

Liens


Voir d'autres communications du même compte rendu (447)
Voir le compte rendu de la conférence