Analyse de l'environnement thermique et optimisation de la distribution d'air pour une salle de données typique.

[In Chinese. / En chinois.]

Auteurs : GAO C., YU Z., WU J.

Type d'article : Article

Résumé

Presents the evaluation indices of thermal environment in data rooms. Taking a typical data room as example, through field test and CFD simulation of the thermal environment, finds cooling waste. Two strategies of adding vertical partitions above the rack on cold aisle side and partly enclosing cold aisles are adopted to improve air distribution based on the original configuration. The results of CFD simulation indicate that the two strategies are both effective, while the latter limits the cold air in the cold aisles to a larger extent, and provides enough cold air to the servers. Therefore, it gets better performance in cooling efficiency improvement.

Documents disponibles

Format PDF

Pages : 101-106

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 30010576
  • Langues : Chinois
  • Source : HV & AC - vol. 43 - n. 281
  • Date d'édition : 09/2013

Liens


Voir d'autres articles du même numéro (3)
Voir la source