Analyse énergétique d'un refroidisseur générateur à compression-absorption échange de chaleur (GAXAC).

Energy analysis of a 1-ton generator-absorber-exchange absorption-compression (GAXAC) cooler.

Résumé

In this work, energy analysis of a generator-absorber-exchange (GAX) absorption-compression system using ammonia-water as a working fluid with a capacity of 3.54 kW (1 ton of refrigeration [TR]) for space conditioning at an optimum degassing range of 0.458 kg of ammonia per kilogram of strong solution is presented. In the GAX absorption-compression cycle, COP values of 1.33 for cooling and 2.33 for heating were obtained, with an internal energy exchange of 4.819 kW. Energy analysis also was carried out for the GAX conventional cycle, and COP values of 0.95 for cooling and 1.95 for heating were calculated, with an internal energy exchange of 4.658 kW for the same capacity. In the GAX section comprising the GAX absorber and the GAX desorber, energy exchange in a GAX absorption-compression cycle is 19% higher than in a GAX conventional cycle. Comparison of GAX absorption-compression and GAX conventional cycles revealed that the GAX compression-absorption cycle gives a 27% higher COP value than the GAX conventional cycle. The results from this study and the published results in the literature are compared and a reasonable agreement is observed.

Détails

  • Titre original : Energy analysis of a 1-ton generator-absorber-exchange absorption-compression (GAXAC) cooler.
  • Identifiant de la fiche : 2009-2354
  • Langues : Anglais
  • Source : ASHRAE Transactions. Papers presented at the 2009 ASHRAE Winter Conference: Chicago, Illinois, January 2009. Volume 115, part 1.
  • Date d'édition : 25/01/2009

Liens


Voir d'autres communications du même compte rendu (20)
Voir le compte rendu de la conférence